Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 08/28/2012 | ELECTRIC - RECONNECT | Denied | 1. BL LUGGING ON SERIVCE DISC. SW TOP AND BOTTOM NOT ALLOWED 2. RECEPTS IN BACK SHOULD IN W.P BOX AND COVERS, GFI PROTECTION, 3. SUP PANEL OUTSIDE NORTH WALL MISSING DEAD FRONT, WIRING AND TERMINATIONS NOT TO CODE INSIDE PANL, RESUPPORT CONDUIT 4. UNSUPPORTED ROMEX WIRING METHOIDE NOT TO CODE, STOREROOM 5. PROVIDE ACCESS TO NORTH STORAGE AREA AND RESTROOMS OUTSIDE 6. WIRING FOR RESTROOM CTS OUTSIDE EAST AREA NOT TO CODE(SWITCHBOX) 7. EXPOSED ROMEX OVER BAR COUNTER (EAST BLD) 8. PROVIDE LADDER FOR ROOF INSPECTIONS ELECTRICAL TO CHECK OUT ROOF ALSO TO REPAIR ANY CODE VIOLATIONS PRIOR TO NEXT INSPECTIONS. |