Permit: T12CM05225

Parcel: 141312090

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T12CM05225

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2012 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
09/05/2012 PLUMBING - YARD WTR LINE/TEST Partial Approval 1. PEX piping not connected at meter. Note: Be sure and keep all piping capped off. 2. See section 306.1 2006 UPC- Buried piping to be supported throughout its entire length. 306.2- Continous load bearing support. Bell holes, hub holes, and coupling holes, shall be provided at points where the pipe is joined. 306.2.2 Rock removal. 306.3 Backfilling.,
09/04/2012 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*