Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |