Permit: T12CM05181

Parcel: 105110710

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T12CM05181

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2012 FIRE - ALARM FINAL Approved
12/03/2012 FIRE - ALARM FINAL Denied 1. Need lock out on breaker #3 in Panel "B"
2. Duct detector for A/C unit #2 (label on A/C unit on roof) failed to shut down was on delay needs to shut immediately, unit shorted out need to test again for proper shut down NO DELAY. Only tested returned air - all other A/C units passed.
3. Tamper switch - Passed
4. Flow switch - Passed
5. Fire panel - Passed
6. Pull stations - Passed
7. Smoke detector above panel - Passed
8. Ground fault - Passed
9. Low Battrey - passed
10. Loss phone line - Passed
11. Signals received at monitoring site - Passed