Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12CM05181
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2012 | FIRE - ALARM FINAL | Approved | ||
12/03/2012 | FIRE - ALARM FINAL | Denied | 1. Need lock out on breaker #3 in Panel "B" 2. Duct detector for A/C unit #2 (label on A/C unit on roof) failed to shut down was on delay needs to shut immediately, unit shorted out need to test again for proper shut down NO DELAY. Only tested returned air - all other A/C units passed. 3. Tamper switch - Passed 4. Flow switch - Passed 5. Fire panel - Passed 6. Pull stations - Passed 7. Smoke detector above panel - Passed 8. Ground fault - Passed 9. Low Battrey - passed 10. Loss phone line - Passed 11. Signals received at monitoring site - Passed |