Permit: T12CM05179

Parcel: 125171280

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/21/2012 BUILDING - FINAL Approved OK SOLAR DGC RESD
09/20/2012 BUILDING - FINAL Partial Approval 1. GROUNDING ELECTROD BOND JUMPER LOOSE-ALSO GROUNDING ELECRODE CONDUCTOR TO BE #8-250.66
2. NEED TORQUE VERIFICATION- PROVIDE ON COMPANY LETTER HEAD
OTHER ITEMS * NOTE: IN FUTURE ALL WARNING LABELS TO BE ON COVERS OUTSIDE
09/17/2012 BUILDING - FINAL Denied 1. MAINTAIN WORKING SPACE IN FRONT OF DISCONNECT
2. HIGHEST BREAKER NOT OVER 6'7"
3. NEED LABELING PER 690.17
4. PROPERLY LABEL BREAKERS PER 408.4
5. CLEAN SURFACE UNDERGROUND BARS 250.12
6. TIGHTEN LOOSE CABLE FITTINGS
7. PLEASE VERIFY TORQUE SETTINGS FOR ROOF HWARDWARE
8. GAS BOND TO BE INTERIOR SIDE PIPING 250.104