Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2012 | EXCAVATION/LAYOUT REBAR & ZON | Approved | ||
| 09/21/2012 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | 1. ALL PLUMBING AND ELECTRICAL FOR STEEL CONEX COMPRESSORS NOT SHOWN ON PLAN OR APPROVED WILL NEED 3RD PARTY NRTL EVALUATION FOR CONEX UNIT APPEARS TO BE PREFABRICATED (NO LISTING) 2. LIGHTS MISSING AT DISPENSERS (CANOPY) 3. VERIFY COMPLIANCE WITH 541.13 514.11 INSPECTION 4. NEED ALL SEAROFFS OPENED FOR 5. ESD BUTTON LOCATION SHALL COMPLY WITH 514.111 C |
|
| 09/20/2012 | EXCAVATION/LAYOUT REBAR & ZON | Denied | NO ACCESS NO MSG |