Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T12CM05125
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/27/2012 | BUILDING - FINAL | Denied | 1. EXPOSED ARMAFLEX TO PROTECTED FROM SUN LITE 2. REMOVE SERVICE DISCONNECT LABELS AT A/C'S 3. SECURE T STAT BOXES 4. BONDING JUMPER TO BE SIZED PER 250.66 MAN DISCONNECTS 5. PANEL DIRECTORY TO BE PERMANENT 6. INADEQUATE ILLUMINATION AT INTERIOR SUB PANEL 7. HANDRAIL TO BE CONTINIOUS 8. VERIFY LISTING OF DIMMING UNIT 9. FINISH FLOURSCENT DISCONNECTS 10. SUPPORT SPEAKER CABLE BEHIND SCREEN 11. FINISH SINKS 12. NEED EXHAUST FAN ADDED TO REPORT 4. BONDING |
|
11/26/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
11/08/2012 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
11/07/2012 | BUILDING - FINAL | Not ready for Inspection | SEE BLDG OFFICIAL FOR TCO | |
11/06/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/02/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/15/2012 | BUILDING - FINAL | Not ready for Inspection | 1. SECURE PVC IN WALLS & VERIFY USAGE IN A PLACE OF OCCUPANCY 2. SECURE M/C CABLES IN WALLS 3. REBAR NOT AS DETAIL 4. NEED ELECTRIC PLANS FOR STAIR SEATING AREA RECEPTACLES, LIGHTS, AND ROW LIGHTING(LV) |