Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/13/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1(GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS - NO MECHANICAL SPLICES 2) USE APPROVED FITTINGS FOR DRYER RACEWAY 3) SUPPORT RISERS 4) PROPERLY INSTALL GROUND ROD CLAMPS 5) TIGHTEN LOOSE FITTINGS. |
|
| 08/23/2012 | ELECTRIC - FINAL | Denied | 2 PANELS INSTALLED WITHOUT GROUNDING ELECTRODES. PROVIDE 2-8 GROUND RODS MIN. 6' APART. CONNECT EACH PANEL TO GROUNDING ELECTRODES. |