Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/20/2012 | ELECTRIC - FINAL | Denied | 1) SERVICE CANNOT BE PARTIALLY UPGRADED. MIN. RESIDENTIAL INCREASE IS 100AMP PER CODE. NEW 125 AMP SERVICE PANEL WITH 8 NEW 20 AMP CRKT BREAKERS ON OLD 30 AMP METER BASE. ALSO NO MAIN BRKR, RED WIRE NUTS TO SMALL, 30 AMP FUSE DISC. SW NOT APPROVED AS J-BOX. UPGRADE COMPLETE SYSTEM-110.3 NEC. 2) BOND WATER AND GAS PIPING. 3) VERIFY REWIRING OF DWELLING HAS BEEN APPROVED, INSPECTED, PERMIT ON FILE, PLANS? OBTAIN LICENSED OR QUALIFIED ELECTRICIAN. |