Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 08/10/2012 | ELECTRIC - RECONNECT | Denied | REPLACE DAMAGED RECEPTACLE. PROVIDE A LIGHT GLOBE OVER CLOSET LIGHT. REMOVE CORD AND PLUG LIGHT ON OUTSIDE OF HOUSE O HARD WIRE. FILL IN OPEN KNOCKOUT AT PANEL FILL IN OPEN SPACES IN PANEL DEAD FRONT. DO NOT SPLICE CONDUCTORS WITH TAPE INSIDE PANEL. PROVIDE SCREWS IN PANEL DEAD FRONT. ALL OUTDOOR RECEPTACLES MUST BE GFI PROTECTED. PROVIDE A ROMEX CONNECTOR AT RECEPTACLE IN CARPORT. REPLACE ANY MISSING COVER PLATES. |