Permit: T12CM04912

Parcel: 11016221A


Addresses:

6255 E GRANT RD


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T12CM04912

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2012 BUILDING - FINAL Approved IVRS - Inspection :*
11/01/2012 BUILDING - FINAL Partial Approval VENT ON CONDENSATE DRAIN MUST BE DOWNSTRAM OF TRAP
SUPPORT OR SECURE EXPANSION TANK AT WATER HEATER
PROVIDE AIR BALANCE REPORT AND CLORNATION REPORT OK TO REMOVE DUCT SMOKE DETECTOR
LABEL EQUIPMENT PANEL TRANSFORMERS, DISCONNECTS ARC FLASH LIFTS
BOND AT CONCENTRICS OVER 250V 250.97
REVISE LIGHTING PLANS FICTURES LOADS, CALVES