Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2012 | BUILDING - FINAL | Partial Approval | VENT ON CONDENSATE DRAIN MUST BE DOWNSTRAM OF TRAP SUPPORT OR SECURE EXPANSION TANK AT WATER HEATER PROVIDE AIR BALANCE REPORT AND CLORNATION REPORT OK TO REMOVE DUCT SMOKE DETECTOR LABEL EQUIPMENT PANEL TRANSFORMERS, DISCONNECTS ARC FLASH LIFTS BOND AT CONCENTRICS OVER 250V 250.97 REVISE LIGHTING PLANS FICTURES LOADS, CALVES |