Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2013 | FIRE - FINAL | Approved | ||
| 03/26/2013 | FIRE - FINAL | Partial Approval | OKAy to use units 45-47-49-51. Tested one duct detector for units 45-47-49-51 A/C unit did shut down and signal did go to main panel as trouble. |
|
| 02/13/2013 | FIRE - FINAL | Partial Approval | Okay to use remodeled Pt. rooms A/C unit (west side) tested duct detector passed set fire alarm sytem off.. All holes patched and doors have seals for smoke control. |
|
| 02/07/2013 | FIRE - FINAL | Denied | Before Temp C of O will be given: Need to smoke proof hallways and doors need gaskets to keep smoke out. A/C unit smoke need to be tied in the fire alarm system |