Inspection History: PLUMBING - MEDICAL GAS/TEST

Date Description Inspector Results Comments
08/15/2013 PLUMBING - MEDICAL GAS/TEST Approved PER RMYERS
07/09/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1 1/4" MEDGAS BELOW GROUND OK TO BACKFILL
05/14/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval Rooms #44, #46, #48, #50, and #52 Med gas in walls to corridor OK. Isolate metallic piping from other metals.
05/07/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
05/07/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval CHECKING LAYOUT
04/04/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*ZONE TEST= OXYGEN 150 TEST
VACUUM 150 TEST
04/03/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval RMS 37,39,41,43 MED GAS IN WALLS TO OUTLETS
04/02/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :* AT MECHANICAL SUPPLY- FRAME WALL FOR ELECTRIC PANELS
03/27/2013 PLUMBING - MEDICAL GAS/TEST Not ready for Inspection
03/25/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. MEDICAL LOG IS TO BE AN ONSITE FOR INSPECTION OVER HEAD CONNECTIONS AT ZONE VALVE
03/18/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*MED GAS EXTENDED TO ZONE VALUE PLUMBERS TAPE HAS NO APPROVAL FUNCTION IN MED GAS
03/12/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. #45, #47, #49, and #51 corridor patient piping from zone valve connected. Mains to the zone valve install today.
03/11/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Rooms 45 and 47 sheetrock nailing OK Med Gas overehead in corridor to room 49.
03/08/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Cart OK. Exterior piping OK. Daily log.
03/06/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. EOSE box hung today.
03/04/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
02/28/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Rooms #45, #47, #49 Medical Gas these rooms have 150# test from outlets to mains in corridor.
02/27/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Rooms #51 and #53 Med. Gas from outlet to mains. Med Gas cart OK. Daily log OK.
02/26/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
01/31/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Vacuum from mechanical room to corridor OK. Vacuum and oxygen in corridor. ESOE stubbed out of building. 2- one inch lines stubbed out of building for bulk tank. Material storage OK. Tanks OK.
01/30/2013 PLUMBING - MEDICAL GAS/TEST Not ready for Inspection
01/29/2013 PLUMBING - MEDICAL GAS/TEST Not ready for Inspection IVRS - Inspection :*
01/25/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Medical Gas labeling to be minimum required by code, plus in each bay between studs.. Medical Gas in corridor to rooms #54, #56, #58.
01/24/2013 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. Existing, unapproved Med. Gas and Vacuum piping removed. New system in Room #58. Gang box OK. Tank storage OK.