Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12CM04692
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2012 | FIRE SPKLR - FINAL | Approved | ||
12/18/2012 | FIRE SPKLR - FINAL | Denied | Painted sprinkler heads in the following areas: 1.) Loading dock area by roof ladder 2.) By 3rd column from south wall then 3 more heads on same line going east ward. 3.) By new concentrail A/C unit 4.) By PF Tucson wall 5.) In women's bathroom back north corner 6.) 2nd floor mezzanine taped and painted south wall windows 1.) Straighten sprinkler piping on 2nd floor mezzanine where drops were removed. 2.) Two sprinkler heads to close to each other by the northwest stairs 2nd floor mezzanine and 1st floor southwest corner by the PF Tucson wall 3.) Correct sprinkler coverage in the large storage room 2nd floor and by the stairs going down to 1st floor northeast. 4.) Correct sprinkler coverage in the sun tanning rooms blocked by units x5 |