Permit: T12CM04649

Parcel: 14027048A


Addresses:

2850 E GANLEY RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/27/2012 ELECTRIC - FINAL Partial Approval RELOCATE EXISTING JUNCTION BOX BEING MADE INEXCESSIBLE BY NEW COLUMN
08/27/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/20/2012 ELECTRIC - FINAL Not ready for Inspection 1) 2 1/2" LOCKNUT IN BACKWARDS AT NEW DISC. SW NIPPLE INTO GUTTER.
2) REMOVE EQUIP. GROUND ON LINE SIDE OF DISC. SW
3) HUB TO BE APPROVED FOR GROUNDING AT SERVICE (4")
110-3
250-4-6 >NEC
250-92