| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2012 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 08/22/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | OK PVC 'PC' | |
| 08/20/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1) 2 1/2" LOCKNUT IN BACKWARDS AT NEW DISC. SW NIPPLE INTO GUTTER. 2) REMOVE EQUIP. GROUND ON LINE SIDE OF DISC. SW 3) HUB TO BE APPROVED FOR GROUNDING AT SERVICE (4") 110-3 250-4-6 >NEC 250-92 |