Permit: T12CM04649

Parcel: 14027048A


Addresses:

2850 E GANLEY RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/05/2012 ELECTRIC - INTERMEDIATE Approved
08/20/2012 ELECTRIC - INTERMEDIATE Partial Approval 1) 2 1/2" LOCKNUT IN BACKWARDS AT NEW DISC. SW NIPPLE INTO GUTTER.
2) REMOVE EQUIP. GROUND ON LINE SIDE OF DISC. SW
3) HUB TO BE APPROVED FOR GROUNDING AT SERVICE (4")
110-3
250-4-6 >NEC
250-92
08/06/2012 ELECTRIC - INTERMEDIATE Partial Approval OK 2.5" CONDUIT TO GUTTER DISC. SW
OK 3/4" EMT FOR PANEL AT WEST PLASMA TABLE WILL NEED REVISION
OWNER WILL USE BLD. STEEL TO GROUND PLASMA TABLE IN LEU OF UFOR.
08/02/2012 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled