Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM04649

Parcel: 14027048A


Addresses:

2850 E GANLEY RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
09/05/2012 ELECTRIC - UFER Approved
08/20/2012 ELECTRIC - UFER Partial Approval 1) 2 1/2" LOCKNUT IN BACKWARDS AT NEW DISC. SW NIPPLE INTO GUTTER.
2) REMOVE EQUIP. GROUND ON LINE SIDE OF DISC. SW
3) HUB TO BE APPROVED FOR GROUNDING AT SERVICE (4")
110-3
250-4-6 >NEC
250-92
08/02/2012 ELECTRIC - UFER Cancelled IVRS - RI canceled