Permit: T12CM04612

Parcel: 130181520

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/28/2012 ELECTRIC - SERVICE UPGRADE Approved OK PER ELECTRIC FINAL
12/11/2012 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
11/23/2012 ELECTRIC - SERVICE UPGRADE Denied 1. SERVICE INSTALLED NOT TO CODE 245
2. ELECTRICIAN SERVICES RECOMMANDED
3. GROUND RODS TO BE BELOW GROUND LEVEL
4. GROUNDING ELECTRODE TO BE LANDED ON GROUND BAR
5. WATER AND GAS BOND MISSING
6. J.BOX MISSING BREAKER BLANK OR BREAKER