Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAST BRAKE TO HAVE THREADED PIPE NOT DOWN CONNECTORS 2) REDUCTING WASHERS INSTALLED BACKWARDS 3) GROUNDING EQUIPMENT CONDUCTOR TO BE PER 250.122 4) FILL UNUSED OPENING BACK OF JUNCTION BOX 5) LOOSE FITTINGS 6) PLEASE IDENTIFY GROUNDED CONDUCTORS WITH TAPE 7) RISER HARDWARE TO BE 1/4" MINIMUM *POWER ENERGIZED WITHOUT CLEARANCE |