Permit: T12CM04567

Parcel: 114500210


Addresses:

8650 E WOODLAND RD

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/18/2013 BUILDING - FINAL Approved IVRS - Inspection :*
05/09/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/09/2013 BUILDING - FINAL Denied 1. TIGHTEN LUGS
2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICES
3. SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL
4. LABEL HIGH LEGS & PANEL PER CODE
5. SURGE ARRESTER DOUBLE TAPED
6. DATA BOX & INTERIOR PLUG STRIP NOT LISTED
7. SECURE CONDUIT SUPPORTS TO ROOF WITH SEALANT
8. PLANS NOT REFLECTING OF SERVICE INSTALLED - NEED REVISED
03/19/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REJECTION CLIP MISSING
2. BOND BUSHING AT PANEL MISSING
3. CONNECTOR TO LB AT AC METER DISCONNECT NOT TO CODE
4. PVC TO BE 18" IN TRENCH
5. SUB.PANEL GROUND BAR TO BE BONDED
6. WIRES AND STRAPES EXPOSED