Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/09/2013 | BUILDING - FINAL | Denied | 1. TIGHTEN LUGS 2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICES 3. SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 4. LABEL HIGH LEGS & PANEL PER CODE 5. SURGE ARRESTER DOUBLE TAPED 6. DATA BOX & INTERIOR PLUG STRIP NOT LISTED 7. SECURE CONDUIT SUPPORTS TO ROOF WITH SEALANT 8. PLANS NOT REFLECTING OF SERVICE INSTALLED - NEED REVISED |
|
| 03/19/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REJECTION CLIP MISSING 2. BOND BUSHING AT PANEL MISSING 3. CONNECTOR TO LB AT AC METER DISCONNECT NOT TO CODE 4. PVC TO BE 18" IN TRENCH 5. SUB.PANEL GROUND BAR TO BE BONDED 6. WIRES AND STRAPES EXPOSED |