Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* BEDROOMS MISSING SOMOK DETECTORS BROKEN OUTLETS AND MISSING COVER PLATES OUT HOUSE LITGHT J BOXES WIRES HANGING DOWN WITH OUT WIRE AND NUTS AN PLASTIC BUSINGS TO PROTECT WIRES KITCHEN STOVE J BOX HAS R O SEAL MISSING AND MUD RING KITCHEN OUTLET TO BE MOUNTED AND WIRES SPLICED WITHOUT BOX SERVICE PANEL MISSING DEAD FRONT MATERIAL WIRE LOOSE AND BURNED AT END ALSO MISSING ? SEAL ON BOTTOM CIRCUIT IN PANEL MISSING WIRE NUTS ON BREAKERS GROUNDING ELECTRODE MISSING |