Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T12CM04482
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/21/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/19/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/14/2012 | MECHANICAL - FINAL | Denied | 1. FINISH RECEPT COUNTER -STRAP M/C 12"OF BOXES 2. FINISH OFFICE FURNITURE- VERIFY 605.5&7 3. NEED CIRCUIT DIRECTORIES PER 408.4 4. ONLY ONE CONDUCTOR TO TERMINAL LUG IN XFMR"?" 5. DISCONNECTING MEANS NEEDED FOR INSTA HOT UNDER SINK. 6. BOXES MORE THAN 1/4 " OR 1/8" 312.20 & 21 NEED RECEPTACLES 7. NEED BOND BUSHING AT BUSS PLUG DISCONNECT 250.97 & LABEL 8. FLOOR BOXES NEED FIRE PENETRATION RATIO 9.CHECK BM LIGHT PER 700.12 (F) 10. NEED AIR BALANCE REPORT & CHLORINATION REPORT |
|
11/13/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/09/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |