Permit: T12CM04482

Parcel: 12701005D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T12CM04482

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/21/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/19/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/14/2012 MECHANICAL - FINAL Denied 1. FINISH RECEPT COUNTER -STRAP M/C 12"OF BOXES
2. FINISH OFFICE FURNITURE- VERIFY 605.5&7
3. NEED CIRCUIT DIRECTORIES PER 408.4
4. ONLY ONE CONDUCTOR TO TERMINAL LUG IN XFMR"?"
5. DISCONNECTING MEANS NEEDED FOR INSTA HOT UNDER SINK.
6. BOXES MORE THAN 1/4 " OR 1/8" 312.20 & 21 NEED RECEPTACLES
7. NEED BOND BUSHING AT BUSS PLUG DISCONNECT 250.97 & LABEL
8. FLOOR BOXES NEED FIRE PENETRATION RATIO
9.CHECK BM LIGHT PER 700.12 (F)
10. NEED AIR BALANCE REPORT & CHLORINATION REPORT
11/13/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/09/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*