Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2012 | ELECTRIC - FINAL | Denied | GATE LOCKED RESCHEDULE INSPECTION | |
| 07/25/2012 | ELECTRIC - FINAL | Partial Approval | TIGHTEN LOOSE FITTINGS - LOAD SIDE | |
| 07/24/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BRACE RISER CONDUIT WITH A VC LISTED BRACE GROUNDING ELECTRIC SYSTEM NEED TO TIE INTO SERVICE PANEL NOT SUB PANEL SUPPORT CONDUITS PER CODE SECURELU CIRCUIT BREAKERS IN PANELS TO MATCH MANUF BRAND SERVICE PANEL NEEDS TO BE INSTALLED SQUARE WITH OTHER ENCLOSURES TO ENSURE PROPER SEATING OF FITTINGS INSTALL EQUIPMENT GROUND WITH FEEDER TO SUB PANEL BUSINGS REQUIRED ON CONNECTORS BOND WATER AND GAS PIPING |