Permit: T12CM04388

Parcel: 121060350


Addresses:

5551 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/15/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
08/13/2012 ELECTRIC - RECONNECT Partial Approval FINISH #1 AND # 2
08/08/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUB PANEL IS NON GROUNDED- CONDUCTORS COLOR TO REFLECT UNINSULATED NEUTRAL
2) GROUNDED RECEPTACLES ON NON GROUNDED CIRCUITS
3) NEW RECEPTACLES AT TILE MORE THAN 1/4" NEED ARE SHEILDS
*OLD WRITE UP NOT ON SITE
07/20/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*