Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/15/2012 | ELECTRIC - FINAL | Partial Approval | FINISH 7,8,&12 | |
| 08/10/2012 | ELECTRIC - FINAL | Denied | 1) NEED APPROVED MOUNTING HARDWARE-DRYWALL SCRES NOT APPROVED 2) FINISH ADDITIONAL CIRCUITS AND LABEL CIRCUITS 3) CORRECTLY TERMINATE AND IDENTIFY UNINSULATED NEUTRAL 4) GAS BOND TO BE TO INTERIOR PIPING 5) SECURE GROUNDING CONDUCTOR TO BUILDING 6) RECEPTACLE COVER TO BE WEATHER RESISTANT WHETHER OR NOT PLUGGED INTO 406.8 7) MAINTAIN WORKING SPACE AT SERVICE 110.26 8) PLEASE PROVIDE ROOF ACCESS TO INSPECT 9) VERIFY 2ND GROUND ROD 10) REDUCING WASHER INSTALLED BACKWARDS 11) RISER HARDWARE TO BE 1/4" MINIMUM 12) NEED LISTED MAST BRACE KIT 13) NO SERVICE CONDUCTORS INSTALLED |