Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM04385

Parcel: 133181390


Addresses:

7052 E EDGEMONT ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/16/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/15/2012 ELECTRIC - SERVICE UPGRADE Partial Approval FINISH 7,8,&12
08/10/2012 ELECTRIC - SERVICE UPGRADE Denied 1) NEED APPROVED MOUNTING HARDWARE-DRYWALL SCRES NOT APPROVED
2) FINISH ADDITIONAL CIRCUITS AND LABEL CIRCUITS
3) CORRECTLY TERMINATE AND IDENTIFY UNINSULATED NEUTRAL
4) GAS BOND TO BE TO INTERIOR PIPING
5) SECURE GROUNDING CONDUCTOR TO BUILDING
6) RECEPTACLE COVER TO BE WEATHER RESISTANT WHETHER OR NOT PLUGGED INTO 406.8
7) MAINTAIN WORKING SPACE AT SERVICE 110.26
8) PLEASE PROVIDE ROOF ACCESS TO INSPECT
9) VERIFY 2ND GROUND ROD
10) REDUCING WASHER INSTALLED BACKWARDS
11) RISER HARDWARE TO BE 1/4" MINIMUM
12) NEED LISTED MAST BRACE KIT
13) NO SERVICE CONDUCTORS INSTALLED