Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T12CM04303
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2013 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
11/09/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO POUR 4 REMAINING LIGHT POLE BASES AT SWAN ENTRY | |
11/01/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO POUR 3 LIGHT POLE BASIS IN FRONT OF 2930 CANOPY | |
10/31/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/10/2012 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
10/05/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER CONDUITS AT LIGHT POLES AND PLANTERS AT SWAN ENTRY ROUND ABOUT | |
09/28/2012 | ELECTRIC - UNDERGROUND | Partial Approval | RIGID CONDUIT IN FLOWER BED AT FRONT OF 2900 OK TO COVER. RIGID CONDUIT FROM FRONT FOUNTAIN 20' TO CORNER OF BLDG OK | |
09/21/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER ELEC CONDUIT FROM S.F BLVD TO SOUTH DRIVEWAY | |
09/20/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER CONDUIT FROM FT LOWELL TO OLD FOUNTAIN | |
09/18/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER ELECTRICAL CONDUITS FROM 1239 TO 120, OK TO COVER FRONT FT LOWELL ENTRANCE WEST TO AROUND CORNER | |
09/14/2012 | ELECTRIC - UNDERGROUND | Partial Approval | ELECTRICAL UNDERGOUNF FROM FOUNTAIN TO SUITE 139 | |
09/13/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER [HASE ELSE UNDERGROUND FROM FOUNTAIN TO ENTRY AT COOLING TOWER | |
09/12/2012 | ELECTRIC - UNDERGROUND | Partial Approval | 1ST 20' FROM FT LOWELL ENTRANCE TOWARDS SWAN OK TO BACKFILL | |
08/28/2012 | ELECTRIC - UNDERGROUND | Partial Approval | PARTIAL..... LA CONTESA COURTYARD CONDUITS OK TO COVER | |
08/13/2012 | ELECTRIC - UNDERGROUND | Partial Approval | CHECKED GROUND WIRES TO 3 LIGHT POSTS AT FT. LOWELL ENTRANCE | |
08/08/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO BACKFILL CONDUITS FROM ABSTRACT TO LA PLACITA. OK TO BACKFILL RELOCATED LIGHT POLE CONDUIT AT FT. LOWELL ENTRANCE. |
|
08/07/2012 | ELECTRIC - UNDERGROUND | Denied | METALLIC CONDUIT IN THE GROUND MUST BE PROTECTED FROM CORROSION. PROVIDE MINIMUM 18" BURIAL DEPTH ON ALL PLASTIC CONDUIT UNDER WALKWAYS, 24" UNDER PARKING LOTS. 300.5 OK TO COVER 2 CONDUITS IN PEDESTRIAN WALKWAY AT EAST FT. LOWELL. |