Permit: T12CM04299

Parcel: 12510003D


Addresses:

3501 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/12/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/22/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/17/2012 ELECTRIC - FINAL Partial Approval WAITING FOR PLAN REVISIONS
08/15/2012 ELECTRIC - FINAL Denied See detailed listing on site.| 999*
1. M/C CABLE LAYING ON GRID
2. EXTENSION CORD NOT ALLOWED ABOVE GRID 400.7&8
3. M/C TO BE INDEPENDANTLY SUPPORTED 300.11
4. PLANS NOT REFLECTIVE OF WORK INSTALLED
PLEASE REVISE AND SHOW LOADS
5. PLEASE VERIFY LISTING AND LABELING OF "501" SIGN 600.3
6. SUPPORT M/C UPON EXISTING OF WALL