Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T12CM04299
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/22/2012 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | CANCELLED | |
08/17/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | WAITING FOR PLAN REVISIONS | |
08/15/2012 | ELECTRIC - ABOVE CEILING | Denied | See detailed listing on site.| 999* 1. M/C CABLE LAYING ON GRID 2. EXTENSION CORD NOT ALLOWED ABOVE GRID 400.7&8 3. M/C TO BE INDEPENDANTLY SUPPORTED 300.11 4. PLANS NOT REFLECTIVE OF WORK INSTALLED PLEASE REVISE AND SHOW LOADS 5. PLEASE VERIFY LISTING AND LABELING OF "501" SIGN 600.3 6. SUPPORT M/C UPON EXISTING OF WALL |