Permit: T12CM04215

Parcel: 133144820


Addresses:

6573 E VIA CAVALIER

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/21/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/14/2012 ELECTRIC - FINAL Denied The wiring is not complete or does not comply with code.| 245*
1) MAINTAIN WORKING CLEARANCE AT PV SERVICE
2_ STRAP GROUNDING ELECTRODE CONDUCTOR
3) NEED LABELING 690.17 ON A/C DISCONNECT
4) ONLY ONE CONDUCTOR TO TEMINAL LUG- METER SOCKET
5) PROVIDE PHYSICAL PROTECTION ON ROOF FOR #8 GEC
6) SECURE D/C CONDUCTORS ON ROOF
7) NO MORE THAN 360 DEGREE IN CONDUIT RUNS