Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING CLEARANCE AT PV SERVICE 2_ STRAP GROUNDING ELECTRODE CONDUCTOR 3) NEED LABELING 690.17 ON A/C DISCONNECT 4) ONLY ONE CONDUCTOR TO TEMINAL LUG- METER SOCKET 5) PROVIDE PHYSICAL PROTECTION ON ROOF FOR #8 GEC 6) SECURE D/C CONDUCTORS ON ROOF 7) NO MORE THAN 360 DEGREE IN CONDUIT RUNS |