Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2012 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/08/2012 | MECHANICAL - INTERMEDIATE | Denied | -USE APPROVED CONDUIT FITTING RATED FOR OUTDOOR USE. -COAT PVC CONDENSATE FOR UV PROTECTION. -CANNOT READ FUSE SIZE IN DISC. SW. INSERT FUSES AS TO SEE RATING. -I.D. CIRCUIT BREAKER IN PANEL -SUPPORT CONDUIT PER CODE |
|
| 08/02/2012 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | 1) PROVIDE EXTENSION LADDER TO ACCESS ROOF. |