Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2012 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 08/23/2012 | EXT METAL CLIPS/EXT SHEATHING | Denied | COMPLY WITH PREVIOUS NOTES 2,3,5,8,10,&11 | |
| 08/20/2012 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) ALL BOTTOM PLATES TO BE PRESSURE TREATED 2) MISSING SW-1 SHEAR WALLS PER PLAN SEE FRAMING PLAN 3) CHECK ALL SHEAR WALL NAILING 6"OC ALL EDGES TO TOP PLATE 4) ALL SW1 SHEAR PANELS TO BE 68" PER CODE NO OPENINGS 5) H-25 CLIPS MISSING NAILS 6) PROUNE LEDGER DETAIL AT FAMILY ROOM SOUTH WALL OR INSTALL LUG BOLTS EACH SUTD STAGGERED 7) MISSING NAILING THROUGHOUT ROD AND SHEATING 8) B-2 TRUSS CALCS SHOW BEARING WALL SOUTH END 9) PROVIDE FOOT TO LEDGER BY MANUFACTURE PROVIDE COT APPROVED CALCS 10) COMPLY WITH TRUSS LAYOUT FAMILY ROOM 11) REMOVE NAILS FROM 2PT BEARING TRUSS B2 TO MID BEARING BED 3 WALL |
|
| 08/17/2012 | EXT METAL CLIPS/EXT SHEATHING | Denied | PROVIDE COT APPROVED PLANS |