Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/18/2012 | MECHANICAL - FINAL | Not ready for Inspection | CONDENSATE APPEARS TO BE DIRECTLY CONNECTED TO THE SANITARY DRAIN. PIPE TO EXTERIOR OR TO AN APPROVED LOCATION. PROVIDE PROPERLY SOLVENT COMENTED JOINTS | |
| 09/12/2012 | MECHANICAL - FINAL | Not ready for Inspection | PROTECT LINE SORT INSULATION FROM HEAT AT SINGLE WALL VENT. (METAL TAPE, SHOAD, OR B VENT) SUPPORT GAS PIPE. CONDENSATE REQUIRES AN INDIRECT CONNECTION TO SANITARY SEWER (UP STREAM OF P TRAP) LINE SET REQUIRES A FLASHING AT ROOF PENETRATION AND SUPPORT ABV ROOF |