Permit: T12CM04011

Parcel: 135111010


Addresses:

7501 E 35TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/31/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/18/2012 MECHANICAL - FINAL Not ready for Inspection CONDENSATE APPEARS TO BE DIRECTLY CONNECTED TO THE SANITARY DRAIN. PIPE TO EXTERIOR OR TO AN APPROVED LOCATION. PROVIDE PROPERLY SOLVENT COMENTED JOINTS
09/12/2012 MECHANICAL - FINAL Not ready for Inspection PROTECT LINE SORT INSULATION FROM HEAT AT SINGLE WALL VENT. (METAL TAPE, SHOAD, OR B VENT)
SUPPORT GAS PIPE.
CONDENSATE REQUIRES AN INDIRECT CONNECTION TO SANITARY SEWER (UP STREAM OF P TRAP)
LINE SET REQUIRES A FLASHING AT ROOF PENETRATION AND SUPPORT ABV ROOF