Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/21/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/02/2013 ELECTRIC - FINAL Denied 1. expose both ground rods sprinklers on
#4 bare must be ireversable
2. support #4 bare to structure
3. plug unused opening in deadfront
4. 1" conduit not supported also broke concetnric ko must must be sealed *