Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2012 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 07/13/2012 | ELECTRIC - RECONNECT | Denied | BOND SERVICE RISER 250.92 HIGHEST AVAILABLE BREAKER NOT HIGHER THAN 6'7" 240.24 (A) SPLIT BOLT FOR ONLY 2 CONDUCTOR 110.3 SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE ONLY 1 CONDUCTOR PER TERMINAL LUG 110.14 NEED GAS & WATER BONDS 250.104 NO LOADS CONNECTED AT THIS TIME |
|
| 07/02/2012 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* |