Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2012 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection :* |
| 07/11/2012 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 07/05/2012 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 06/29/2012 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
1. Misidentified neutral 2. #14 wire in a 20 amp. breaker. 3. Provide correct breaker for receptacle or remove. 4. Remove power poles or support properly. |