Permit: T12CM03861

Parcel: 120091550


Addresses:

335 E RODEO DR


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T12CM03861

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2012 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/02/2012 PLUMBING - GAS PRESSURE TEST Denied NOTES 3,4,6 AND 8 FROM PREVIOUS
07/30/2012 PLUMBING - GAS PRESSURE TEST Denied (1) PROVIDE LICENSED CONTRACTOR DOING REPLACEMENT DUE TO RENTAL UNIT
(2) PRIMER AND TAPE ALL JOINTS TO CODE
(3) PROVIDE SHUTOFF VALVE AT HOUSE
(4) MISSING 22'-6" RUN OF 3/16" LINE FOR FUTURE FURNACE
(5) PROVIDE NEW MATERIALS THROUGHOUT NEXT DENIAL MAY RESULT IN A REFEE
(6) MISSING SHUTOFF VALVES APPLIANCES
(7) NOT HOLDING TEST
(8) BOND GAS LINE
07/26/2012 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PIPE FITTINGS NOT PREPRIN COATED
07/25/2012 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PIPING NEEDS TO BE 12" TOP PIPE TO FINISH GRADE
COAT AND WRAP FITTINGS AND TOOL MARKS