Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2012 | FIRE - FINAL | Approved | ||
| 08/06/2012 | FIRE - FINAL | Denied | Correct sprinkler coverage in the nail tech room heads are over 8 feet away from wall can not use small room rule. Correct sprinkler head escutcheons throughout building and top of stairs. Lock sprinkler control valve in the open position. |