Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2012 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/21/2012 | MECHANICAL - INTERMEDIATE | Partial Approval | 1. REFRIGERATION PIPING NOT TO BE IN CONTACT WITH GALVANIZED SIDE WALL JACK OR STRAPPING/NAIL PLATES 2. ALL PVE JOINTS TO HAVE PRIMER PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC 3. HORIZ SUPPORT OF PVC NOT TO EXCEED 48" 4. PROVIDE NAIL PLATES WHERE WIRING PASSES THOURGH STUDS AT LESS THAN 1.5" 5. PRESSURE TEST ON SOLAR PIPING OK |