Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T12CM03718
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2013 | SITE - SEWER | Approved | IVRS - Inspection :* | |
11/16/2012 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
11/15/2012 | SITE - SEWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/14/2012 | SITE - SEWER | Denied | SLOPE LEAK FITTINGS COVERED | |
11/09/2012 | SITE - SEWER | Not ready for Inspection | POST YOUR ADDRESS. ULITITY PLAN C150 DOES NOT HAVE MECHANICAL PLAN REVIEW. SEE BOB SHERRY. CODE REQUIRES A WATER TEST PRIOR TO COVERING. PROVIDE APPROVED DRAINAGE FITTINGS FOR VENT CONNECTIONS. INSTALL INTERCEPTOR VENT. TEST INTERCEPTOR. CORRECT SLOPE AT CONNECTIONS. PROVIDE THIN WALL BUSHING ON SDR AT TANK OUTLET. INSTALL CLEANOUTS ON BOTH SIDES OF BW VALVE. |