Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/15/2012 | ELECTRIC - FINAL | Denied | 1. NEED EQUIPMENT BOND JUMPER FOR LIGHTS 2. RECIPTICALS TO BE ATTACHED TO METAL COVERS 3. BOX OVER FILLED 4. SUPPORT EMT 3' FROM BOXES 5. REGROUND JUNCTION BOX ON HOUSE PANEL IN CLOSET IS EXISTING |