| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2012 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 08/23/2012 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/20/2012 | EXT METAL CLIPS/EXT SHEATHING | Denied | PLYWOOD TO FUR OUT RAFTER HANGER TITENS PER PLAN FOR STAIRWALL SHEER 355.1 AND 356.1 DETAIL PER PLAN |
|
| 08/17/2012 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | NOT READY STOPPED INSPECTION, TOO MANY ITEMS TO LIST. -16 D NAILS IN FRONT HOLD DOWN STRAP -NAIL PROTECT PLUMBING AT BOTTOM PLATES WITHIN 1 1/4" -BLOCK AND RENAIL SHEAR ABOVE OVERHEAD DOOR -ANCHOR BOLT NEEDED WITHIN 12" OF PLATE SPLICE NORTH OF UNDERGROUND ELECTRIC -ANCHOR BOLTS NEEDED WITHIN 12" OF 2X6 PLATE SEAMS AT STAIRWAY -COMPLETE ALL DETAILS BEFORE RECALLING TO PREVENT RE-INSPECTION FEE TO BE IMPOSED. |