Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/03/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CAN NOT MODIFY BOX- USE APPROVED BOX FOR EXTENTION 2) POWER STRIP IN DATA BOX NOT LISTED 3) MAINTAIN WORKING SPACE 110.26 4) USE BREAKERS LISTED BY MANUFACTURERS 5) LOCK NOT INSTALLED BACKWARDS ON PANEL L B 6) DISSIMIULAR METAL CONTACT FOR GROUNDING ELECTRODE CONDUCTOR 7) DC RACEWAY TO BE MEATALIC 690.31(E) 8) NEED ROOF ACCESS |