Permit: T12CM03667

Parcel: 133033710


Addresses:

9529 E VENTASO CI


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T12CM03667

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2012 BUILDING - FINAL Approved IVRS - Inspection :*
08/03/2012 BUILDING - FINAL Denied 1) CAN NOT MODIFY BOX- USE APPROVED BOX FOR EXTENTION
2) POWER STRIP IN DATA BOX NOT LISTED
3) MAINTAIN WORKING SPACE 110.26
4) USE BREAKERS LISTED BY MANUFACTURERS
5) LOCK NOT INSTALLED BACKWARDS ON PANEL L B
6) DISSIMIULAR METAL CONTACT FOR GROUNDING ELECTRODE CONDUCTOR
7) DC RACEWAY TO BE MEATALIC 690.31(E)
8) NEED ROOF ACCESS