Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM03633

Parcel: 133310760

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/27/2012 ELECTRIC - SERVICE UPGRADE Approved PER ELEC FINAL
08/22/2012 ELECTRIC - SERVICE UPGRADE Denied 1. SOLAR BREAKER IN SERVICE PANEL NOT LABELED
2. STRAPS ON ROOF 3/4 EMT LOOSE
3. SOLAR PANEL WIRES TOUCHING ROOF
4. LOCK NUT ON INVERTER ON BACKWARDS