Permit: T12CM03601

Parcel: 111030110

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/19/2012 PLUMBING - FINAL Approved ALL CORRECTIONS HAVE BEEN MADE PER APPROVED PLAN
12/17/2012 PLUMBING - FINAL Cancelled IVRS - AP canceled
12/10/2012 PLUMBING - FINAL Denied 1. Gas piping not installed per plan, Will require an approved isometric showing all appliances with BTU and developed length shown. Future tee connections not permitted unless identified on the plan. Plugged tee connections made in lieu of couplings, not permitted. Medium pressure regulator vent to be approved gas material. Ductwork may not be used to support vent. For the gas card- all appliances to be connected unless specifically identified as "future" on the plan. Identify which piping is medium pressure and which is low pressure, and where it occurs.
11/23/2012 PLUMBING - FINAL Cancelled IVRS - RI canceled
11/21/2012 PLUMBING - FINAL Approved IVRS - Inspection :*