Permit: T12CM03601

Parcel: 111030110

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/21/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/08/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection 1) DEMO BACK TO OLD LIGHT AND SEAL
2) RE STRAP EMT
3) VDV TO BE PB4 725.3 AND 8, 800.3 AND 24
4) VERIFY 18" FROM CEILING PER 511.3 (A) (7) FOR CLASSIFICATION
5) VERIFY CLASSIFIED AREA'S ONPLANS
6) ALL NEW WIRING, CIRCUITS, LOADS NEEDED FOR PLAN REVISIONS
PLAN DO NOT RELECT EXISTING NEED TO VERIFY FOR 511.4,7,9,10 AND 16
09/27/2012 ELECTRIC - INTERMEDIATE Partial Approval OK TO CLOSE WALLS