Permit: T12CM03460

Parcel: 114471910

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/19/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/17/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/12/2012 ELECTRIC - FINAL Denied 1, MAINTAIN WORKING SPACE IN FRONT OF INVERTOR DISCONNECT.
2. ELETRIC TO BE 3' FROM GAS VENT
3. NEED ALL LABELING PER 690.17
4. PLEASE OPEN INVERTER DISCONNECT FOR INSPECTION
5. CLEAN SURFACE UNDERGROUND LUGS 250.12
6. NO MORE THAN 360* IN CONDUIT RUNS
7. FILL UNUSED OPENING IN DEAD FRONT COVER 110.12
8. PLEASE PROVIDE OSHA APPROVED LADDER FOR ROOF ACCESS
9. SECURE CABLE TO BOX 312.5(C)
10. PLEASE VERIFY TORQUING OF SCHIRTTER RACK SYSTEMS FOR GROUNDING AND INSTALL.